dc.contributor.author |
ZOUIDJA, El Atra |
|
dc.date.accessioned |
2023-04-05T08:24:33Z |
|
dc.date.available |
2023-04-05T08:24:33Z |
|
dc.date.issued |
2014 |
|
dc.identifier.uri |
https://dspace.univ-ghardaia.edu.dz/xmlui/handle/123456789/5946 |
|
dc.description.abstract |
The purpose of this study is the follow-up assessment of physico-chemical parameters of
treated wastewater in the STEP before and after treatment for five months (January, February,
March, April and May) to study the purification performance of water pollutants.
The results show that the treatment performance are good and are above 60% for most
parameters. In fact, the average rate of drawdown calculated are of the order of 67.10% (MES),
66.2% (DBO5
), 65.24% (DCO), and with fairly acceptable means drawdown rate for the other
parameters 12.9% (N-NH4
+
) , 28.57% (N-NO2
-
), 45.19% (N-NO3
-
) and 13.94% (N2
total) during
the five-month follow-up.
These performances are generally close to the ranges of performance required by Algerian
law and may be improved after a good development and good coverage of lagoons.
The experience of wastewater treatment by stabilization ponds to STEP Kef Dokhan
(Ghardaia) shows the current and acceptable treatment efficiency and facilities, operation and
maintenance are less expensive and more beneficial to the environment. |
EN_en |
dc.language.iso |
fr |
EN_en |
dc.publisher |
Faculté Science de la Nature et de la Vie et Sciences de la Terre - Université de Ghardaïa |
EN_en |
dc.subject |
pollution, sewage treatment plant, STEP, wastewater ,stabilization ponds, Ghardaia. |
EN_en |
dc.subject |
polluants, station d'épuration STEP, eaux usées, lagunage naturel, Ghardaïa. |
EN_en |
dc.title |
Epuration des eaux usées par lagunage naturel de la région de Ghardaia Evolutions et conditions optimales |
EN_en |